AO Smith Water heater Intelli-Vent power-vent models 6 flashes

What it should look like on your machine

then it repeats

6 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Ignition/flame failure. The heater reached its maximum number of ignition retries and is locked out for one hour.

Likely causes

  1. Gas supply turned off or supply/manifold pressure too low
  2. Low supply voltage (must be 115–125 VAC)
  3. Dirty flame sensor or flame sensor not contacting the burner flame
  4. Mispositioned, cracked, or worn hot surface ignitor
  5. Vent pipe oversized for the run, causing turbulence in the combustion chamber

How to fix it — step by step

  1. Cycle power off and on to reset the one-hour lockout before testing.
  2. Confirm gas supply is on and that supply and manifold pressures meet the installation manual; manifold pressure is non-adjustable — if it is off by more than 0.3 in. W.C., replace the Intelli-Vent control.
  3. Confirm supply voltage is 115–125 VAC.
  4. Locate the ignition parts: the burner is under the tank behind the lower access door; the flame sensor is the rod standing in the burner flame at the burner assembly, and the hot surface ignitor is the flat element beside the burner, both wired back to the Intelli-Vent control at the front of the tank.
  5. Clean the flame sensor with ultra-fine steel wool or a Scotch-Brite pad and confirm it sits in a steady burner flame — an oxide-coated rod is the most common cause of this lockout.
  6. Check the ignitor position and inspect its ceramic insulators for cracks; measure ignitor resistance at room temperature and replace the ignitor assembly if it is outside 11.5–18.8 ohms or damaged (power off, its two leads disconnected, mounting screws out, new ignitor handled by its base).
  7. Confirm the vent pipe size matches the manual for the vent length; oversized pipe can cause excessive combustion-chamber turbulence.
  8. If you hand it over, tell the technician: 6 flashes — ignition/flame failure lockout — and whether the sensor was fouled and what the ignitor measured.
  9. Verify after the repair: restore gas, water and power, then open a hot tap and let the heater fire and run for several minutes - the heater should run clean through the whole draw. If it comes back, the repair did not cure it: hand over the point in the sequence where it reappears, because that timing is the diagnosis

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Typical pro repair $228–$1,017

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.