Lochinvar Boiler Knight 81-286 (SMART SYSTEM) Inlet Sensor Fault

What this problem usually means

Inlet Sensor Fault is a manual reset lockout raised when the control reads the inlet sensor as open or shorted. The corrective sequence is wiring first, then the sensor's resistance against Table 3-2A, then the control module. That order matters, because most sensor faults are connection faults.

Likely causes

  1. Control reads the inlet sensor as open or shorted
  2. Inlet sensor wiring disconnected or damaged
  3. Faulty inlet sensor
  4. Faulty control module

How to fix it — step by step

  1. Record the fault before resetting: write down 'Inlet Sensor Fault' exactly as shown on the SMART SYSTEM display, and note that most Knight lockouts need a manual reset with the RESET button on the SMART SYSTEM display after the condition is corrected.
  2. Safety: shut the boiler down, isolate power and close the gas shut-off valve before opening the cabinet or testing wiring. Gas pressure, gas valve and combustion checks are qualified technician work.
  3. Locate the parts: the inlet water temperature sensor is fitted in the boiler inlet waterway and wired to the control module, and the fault is read on the SMART SYSTEM display.
  4. Test: check the wiring to the sensor and make sure it is connected and not damaged, reconnecting or repairing it as needed. Then measure the resistance of the sensor and compare it with Table 3-2A on page 35 of the service manual; a reading outside the table condemns the sensor.
  5. End at the fix: replace the inlet sensor if its resistance is out of range, then press RESET on the SMART SYSTEM display. Wiring and sensor both proven good pinpoints the control module, which is replaced. → Shop the control module at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Lochinvar Boiler Knight 81-286 (SMART SYSTEM) problems

See all Lochinvar Knight 81-286 (SMART SYSTEM) codes & guides →