Bradford White Water heater ICON System (power vent / power direct vent / fan assisted) 6 flashes - 2 flashes

What it should look like on your machine

then it repeats

6 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Pressure switch or temp switch opened during operation: the proving circuit that closed to start the burner dropped out mid-cycle.

Likely causes

  1. Vent blockage developing under operation
  2. Blower losing speed during the cycle
  3. Pressure switch or temp switch failing intermittently

How to fix it — step by step

  1. Check the vent for blockage — a vent that blocks progressively as the blower heats and runs is the classic cause of a circuit that proves at start and drops out mid-cycle.
  2. The pressure switch is mounted at the blower housing on top of the tank, with vinyl tubing to the blower outlet; the temp (vent limit) switch is in the same proving circuit at the blower/vent. Both are reached with the top cover off.
  3. Measure vacuum on the pressure switch during operation, not just at start: vacuum that fades as the cycle runs means the blower or vent is failing under operation; vacuum that holds while the circuit opens condemns a switch.
  4. Verify the blower is spinning up to speed and holding speed through the whole cycle.
  5. Bypass the pressure switch and temp switch for testing only to isolate the device opening — never leave a bypass in place.
  6. Replace the pressure switch, temp switch or blower assembly as isolated (switch: tubing and wires off, screws out, rating matched; blower: power off, vent and wiring disconnected, assembly off the tank top). → Shop the pressure switch at Amazon → Shop the blower assembly at Amazon
  7. Prove a long full heating cycle with the circuit holding throughout.
  8. If you hand it over, tell the technician: 6 flashes–2 — proving circuit opened during operation — and whether the vacuum faded or held while it dropped out.
  9. Verify after the repair: restore gas, water and power, then open a hot tap and let the heater fire and run for several minutes - the heater should run clean through the whole draw. If it comes back, the repair did not cure it: hand over the point in the sequence where it reappears, because that timing is the diagnosis

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $50–$205Typical pro repair $228–$1,017Fixing it yourself typically saves $23–$967

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.