Bradford White Water heater ICON System (power vent / power direct vent / fan assisted) 2 flashes
What it should look like on your machine
then it repeats
2 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Pressure switch not working - closed position: the pressure switch is stuck/welded closed when it should be open before the blower runs.
Likely causes
- Pressure switch tubing or ports blocked/kinked giving a false reading
- Faulty pressure switch stuck closed
- Faulty temperature switch in the proving circuit
How to fix it — step by step
- The pressure switch is mounted at the blower housing on top of the tank, with vinyl tubing to the blower outlet; the temp (vent limit) switch is in the same proving circuit at the blower/vent. Both are reached with the top cover off.
- Inspect the pressure switch tubing and ports and clear any blockage — blow through the tubing and probe the blower outlet port clear; a plugged port holds the switch's diaphragm exactly like a welded contact.
- Measure vacuum on the pressure switch with a manometer during a call: this code is the switch reading closed before the blower runs, so the confirming test is electrical — with the blower off and wires disconnected, the switch contacts must read open. Contacts showing continuity at rest condemn the switch. → Shop the pressure switch at Amazon
- Bypass the pressure switch and temp switch for testing only to isolate which device is stuck closed — the one whose bypass changes the code is the stuck device. Never leave a bypass in place; these are safety proofs.
- Replace the pressure switch (or temp switch, if that is the stuck device): power off, wires and tubing off, mounting screws out, the new switch fitted with its rating matched, tubing and wires back on.
- Prove a full cycle: blower starts, switch proves, burner fires, no 2-flash code.
- If you hand it over, tell the technician: 2 flashes — pressure switch reading closed before the blower runs — and whether its contacts tested closed at rest.
- Verify after the repair: restore gas, water and power, then open a hot tap and let the heater fire and run for several minutes - the heater should run clean through the whole draw. If it comes back, the repair did not cure it: hand over the point in the sequence where it reappears, because that timing is the diagnosis
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Pressure switch.
Shop the Pressure switch at Amazon
Also tied to this fault: Temp switch - Shop at Amazon
Parts that commonly fix it
- Pressure switch$50–$205Shop at Amazon
- Temp switchShop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.
Related Bradford White Water heater ICON System (power vent / power direct vent / fan assisted) problems
- 3 flashes
- 4 flashes
- 5 flashes
- 6 flashes - 1 flash
- 6 flashes - 2 flashes
- 6 flashes - 3 flashes
- 6 flashes - 4 flashes
- 7 flashes
- 8 flashes - 1 flash
- 8 flashes - 2 flashes
- 8 flashes - 3 flashes
- 8 flashes - 4 flashes
See all Bradford White ICON System (power vent / power direct vent / fan assisted) codes & guides →