Carrier Heat pump 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump 25 Error Code

What the 25 code means

Invalid Model Plug — the control does not detect a model plug or detects an invalid model plug, and the manual states the unit will not operate without the correct model plug. Read as 2 short and 5 long flashes on the amber status LED, and on the Infinity Control where fitted. The model plug tells the board the unit size and configuration, so a missing, damaged or wrong plug prevents any compressor or fan operation even though power is present.

Likely causes

  1. Model plug missing after a control board replacement
  2. Wrong model plug installed for the unit size
  3. Damaged or corroded model plug or pins
  4. Outdoor control board not reading the plug correctly

How to fix it — step by step

  1. Record the amber LED pattern before cycling power: count short flashes (0.25 sec, first digit) then long flashes (1.0 sec, second digit), note any Infinity/Evolution wall-control display of the same code, and photograph the rating plate — power cycles and recycling 24V can clear stored codes or defeat the 15-minute retry delay.
  2. Safety: switch the outdoor disconnect OFF and the breaker OFF, verify the unit is dead with a meter before touching wiring, and treat the run capacitor as charged until discharged by a technician — do not open the refrigerant circuit.
  3. Locate the outdoor control board behind the service panel, and the part named in this entry; check access, harness seating, and visible damage, ice, debris, or a clogged indoor air filter first.
  4. With power OFF and verified dead, locate the model plug on the outdoor control board, confirm it is fully seated, and compare its part/resistance identification to the unit model on the rating plate; check pins for corrosion or breakage.
  5. Pinpoint: reinstall the original correct model plug if missing; if the correct plug is seated and undamaged and code 25 remains, the outdoor Control board is the pinpointed failure — technician replacement.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 25 code

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Working on a specific model? The official Carrier manual is on Carrier's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related Carrier Heat pump 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump error codes

See all Carrier 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump codes & guides →