Carrier Heat pump 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump 31 Error Code

What the 31 code means

High Pressure Switch Open — a high-pressure switch trip, shown as 3 short and 1 long flashes on the amber status LED and at the Infinity Control where fitted. The manual directs checking refrigerant charge, outdoor fan operation and coils for airflow restrictions. The board de-energizes the compressor contactor and runs the outdoor fan for up to 15 minutes, then retries; repeated trips escalate toward the code 84 lockout. High pressure stresses the compressor and refrigerant circuit, so this is not a reset-and-ignore fault.

Likely causes

  1. Outdoor coil blocked by dirt, debris or ice restricting airflow
  2. Outdoor fan motor not running or running slowly
  3. Refrigerant overcharge
  4. Restriction in the refrigerant circuit

How to fix it — step by step

  1. Record the amber LED pattern before cycling power: count short flashes (0.25 sec, first digit) then long flashes (1.0 sec, second digit), note any Infinity/Evolution wall-control display of the same code, and photograph the rating plate — power cycles and recycling 24V can clear stored codes or defeat the 15-minute retry delay.
  2. Safety: switch the outdoor disconnect OFF and the breaker OFF, verify the unit is dead with a meter before touching wiring, and treat the run capacitor as charged until discharged by a technician — do not open the refrigerant circuit.
  3. Locate the outdoor control board behind the service panel, and the part named in this entry; check access, harness seating, and visible damage, ice, debris, or a clogged indoor air filter first.
  4. Technician: verify the outdoor fan runs on a call, clean/inspect the outdoor coil, then connect gauges and check charge by the manual's method — pressures alone without airflow checks can mislead; also test the high-pressure switch continuity and harness.
  5. Pinpoint: correct the airflow, fan or charge cause found; if charge and airflow are correct and the switch tests open at normal pressure or its harness is faulty, the switch/harness is pinpointed — refrigerant work is EPA-certified technician only.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 31 code

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Working on a specific model? The official Carrier manual is on Carrier's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related Carrier Heat pump 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump error codes

See all Carrier 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump codes & guides →