Carrier Heat pump 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump 46 Error Code
What the 46 code means
Brown Out (230V) — line voltage was below 187 volts for at least 4 seconds, shown as 4 short and 6 long flashes. The manual states compressor and fan operation are not allowed until voltage rises above 190 volts, and directs verifying line voltage. This is a supply-protection event, not a failed part inside the unit: the board is protecting the compressor from low-voltage damage. A single event after a utility dip may clear itself; repeated 46 events point at the building supply or connections.
Likely causes
- Utility voltage dip or brownout
- Loose or corroded disconnect or breaker connections
- Undersized or damaged supply wiring causing voltage drop under load
- Failing breaker or disconnect contacts
How to fix it — step by step
- Record the amber LED pattern before cycling power: count short flashes (0.25 sec, first digit) then long flashes (1.0 sec, second digit), note any Infinity/Evolution wall-control display of the same code, and photograph the rating plate — power cycles and recycling 24V can clear stored codes or defeat the 15-minute retry delay.
- Safety: switch the outdoor disconnect OFF and the breaker OFF, verify the unit is dead with a meter before touching wiring, and treat the run capacitor as charged until discharged by a technician — do not open the refrigerant circuit.
- Locate the outdoor control board behind the service panel, and the part named in this entry; check access, harness seating, and visible damage, ice, debris, or a clogged indoor air filter first.
- Measure line voltage at the outdoor disconnect with a meter: the manual's thresholds are trip below 187V for 4 seconds and no restart until above 190V; measure again under a compressor start attempt to reveal voltage drop from loose connections.
- Pinpoint: if voltage at the disconnect is low or drops under load, the supply, breaker, disconnect or connections are pinpointed — an electrician/utility issue, not a heat pump part; if supply is steady and correct, have a technician check the board's voltage sensing.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the fault is internal - there is no documented owner fix beyond the steps above. If you're not comfortable taking it apart yourself, a repair shop is the next step.
Parts that commonly fix the 46 code
This fault usually does not need a replacement part - the fix is in the steps above. If your heat pump does need a part, start with the link above.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Working on a specific model? The official Carrier manual is on Carrier's support site — you'll need your model number.
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related Carrier Heat pump 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump error codes
See all Carrier 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump codes & guides →