York Air Conditioner LED1 1 flash, LED2 on steady

What it should look like on your machine

then it repeats

1 flash - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Compressor contactor miswire on the YorkGuard VI demand defrost / outdoor unit control in a York outdoor unit (document 276251-UAI-A-0107, Table 7 Wiring Related Fault Codes). Wiring faults are displayed with LED1 (red) flashing — here 1 flash — while LED2 (green) is on constantly; the X/L output shows 4 flashes. Per the manual, if a compressor wiring error is detected the control will not operate the compressor, and 24 VAC power must be cycled after correcting it.

Likely causes

  1. Contactor wired incorrectly to the outdoor control (M/M1/M2 terminals)
  2. Wiring error made when a component or control was replaced

How to fix it — step by step

  1. Turn off power to the system
  2. Have a technician compare the contactor wiring with the unit wiring diagram and correct it
  3. Cycle 24 VAC power to the control so it re-senses the wiring and clears the lockout

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.