York Air Conditioner LED1 5 flashes, LED2 off

What it should look like on your machine

then it repeats

5 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Low voltage (below 19 VAC) preventing further relay outputs, on the YorkGuard VI demand defrost / outdoor unit control in a York outdoor unit (document 276251-UAI-A-0107, Table 5). LED1 (red) flashes 5 times, LED2 (green) is off and the X/L output is off.

Likely causes

  1. Low 24 VAC supply to the outdoor control (undersized or failing indoor transformer) → Shop the control transformer (indoor, 40 va minimum) at RepairClinic
  2. Loose low-voltage wiring or excessive voltage drop
  3. Short or overload dragging down the control voltage

How to fix it — step by step

  1. Have a technician measure the 24 VAC at the control's R terminal under load
  2. Check low-voltage wiring connections and the indoor transformer rating (the manual notes a minimum 40 VA indoor transformer)
  3. Repair the wiring or replace the transformer as needed

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.