American Standard Heat pump 4A7A6048C1000B heat pump with AccuLink and Charge Assist 6 flashes
What it should look like on your machine
then it repeats
6 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Read on the red Fault LED of the AccuLink outdoor control, and shown at the comfort control as ERR 67. The Summary of Alert Code and Charge Assist LEDs in the American Standard Service Facts lists six flashes as a coil temperature sensor fault, out of range - open or shorted. The coil sensor tells the control the outdoor coil's temperature, which the demand defrost logic compares with ambient temperature to decide when frost needs melting and when defrost can end. It matters because a blind control either defrosts on a crude fallback or not correctly at all, costing heating capacity all winter.
Likely causes
- Coil temperature sensor open or shorted
- Sensor loose, corroded or no longer clipped tightly to the outdoor coil
- Damaged sensor lead or connector at the outdoor control board
- Failed sensor input on the outdoor control board
How to fix it — step by step
- Record the code before cycling power: count six flashes and record ERR 67 before cycling power. Power-cycling can clear, change or recount the fault, so note the display, operating mode and outdoor temperature first.
- Safety: turn the system off, open the outdoor disconnect and breaker, verify with a meter that the unit is dead before touching wiring, and stay clear of the run capacitor terminals - a capacitor can hold a shock charge with power off.
- Locate the part: find the coil sensor clipped to the outdoor coil tubing, wired back to the outdoor control board in the control box; check the clip has not sprung loose
- Test: power off and measure sensor resistance against the Service Facts chart at the measured coil temperature - open, shorted or off-chart confirms failure; a good reading with a loose clip is an installation fault, not a bad sensor
- End point: reclip a sound sensor tightly or replace a failed one. Persistent six flashes with a verified-good sensor point to the outdoor control board, a pro replacement. Any work that opens the sealed refrigerant circuit, adjusts charge, or replaces a refrigerant pressure device is EPA-certified technician work only. → Shop the control board at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the Thermistor.
Also tied to this fault: Defrost sensor - Shop at Amazon; Control board - Shop at Amazon
Parts that commonly fix it
- Thermistor$25–$80Shop at Amazon
- Defrost sensor$25–$80Shop at Amazon
- Control boardShop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related American Standard Heat pump 4A7A6048C1000B heat pump with AccuLink and Charge Assist problems
- 7 flashes
- ERR 90
- 1 flash
- 10 flashes
- 11 flashes
- 12 flashes
- 13 flashes
- 14 flashes
- 17 flashes
- 18 flashes
- 2 flashes
- 3 flashes
See all American Standard 4A7A6048C1000B heat pump with AccuLink and Charge Assist codes & guides →