American Standard Heat pump 4A7A6048C1000B heat pump with AccuLink and Charge Assist 13 flashes
What it should look like on your machine
then it repeats
13 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Read on the red Fault LED of the AccuLink outdoor control, and shown at the comfort control as ERR 67. The Summary of Alert Code and Charge Assist LEDs in the American Standard Service Facts lists thirteen flashes as an external outdoor temperature sensor fault, out of range - shorted, distinguishing it from the five-flash fault for the unit's own ambient sensor. The manual also notes the control does not fall back to this external sensor for defrost or Charge Assist when the main ambient sensor fails. It matters because systems using the external sensor for displayed or control outdoor temperature will show wrong values until it is replaced.
Likely causes
- External outdoor temperature sensor shorted
- Sensor wiring shorted together or to ground along its run
- Water ingress or physical damage at the external sensor
- Failed sensor input on the outdoor control board
How to fix it — step by step
- Record the code before cycling power: count thirteen flashes and record ERR 67 before cycling power. Power-cycling can clear, change or recount the fault, so note the display, operating mode and outdoor temperature first.
- Safety: turn the system off, open the outdoor disconnect and breaker, verify with a meter that the unit is dead before touching wiring, and stay clear of the run capacitor terminals - a capacitor can hold a shock charge with power off.
- Locate the part: trace the external outdoor temperature sensor - mounted away from the unit where the installer placed it - and its cable back to the outdoor control board
- Test: power off and measure the sensor's resistance against the Service Facts chart at the actual outdoor temperature; a near-zero reading confirms the short the code describes, and isolating the sensor from its cable shows whether the short is in the sensor or the wiring
- End point: replace a shorted sensor or repair the shorted cable run, whichever the isolation test condemns. A verified-good sensor and cable that still fault point to the outdoor control board. Any work that opens the sealed refrigerant circuit, adjusts charge, or replaces a refrigerant pressure device is EPA-certified technician work only. → Shop the control board at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the Thermistor.
Also tied to this fault: Control board - Shop at Amazon
Parts that commonly fix it
- Thermistor$25–$80Shop at Amazon
- Control boardShop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related American Standard Heat pump 4A7A6048C1000B heat pump with AccuLink and Charge Assist problems
- 14 flashes
- 17 flashes
- 18 flashes
- 2 flashes
- 3 flashes
- 4 flashes
- 5 flashes
- 6 flashes
- 7 flashes
- ERR 90
- 1 flash
- 10 flashes
See all American Standard 4A7A6048C1000B heat pump with AccuLink and Charge Assist codes & guides →