American Standard Heat pump 4A7A6048C1000B heat pump with AccuLink and Charge Assist 7 flashes
What it should look like on your machine
then it repeats
7 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Read on the red Fault LED of the AccuLink outdoor control, and shown at the comfort control as ERR 79. The Summary of Alert Code and Charge Assist LEDs in the American Standard Service Facts lists seven flashes as a low pressure cut-out fault, open outside the defrost cycle, in two forms: a hard lockout, reset by cycling power, and a short lockout, during which the comfort control shows its Wait indication. It matters because the cut-out protects the compressor from low refrigerant pressure; the hard-lockout form means the trips have repeated enough that the control will no longer self-recover.
Likely causes
- Low refrigerant charge from a leak
- Outdoor airflow restriction or iced coil in heating
- Indoor airflow restriction or dirty air filter in cooling
- Low pressure cut-out switch or its wiring opening falsely
How to fix it — step by step
- Record the code before cycling power: count seven flashes, note heating or cooling, and whether the comfort control shows Wait, which marks the short-lockout form. Power-cycling can clear, change or recount the fault, so note the display, operating mode and outdoor temperature first.
- Safety: turn the system off, open the outdoor disconnect and breaker, verify with a meter that the unit is dead before touching wiring, and stay clear of the run capacitor terminals - a capacitor can hold a shock charge with power off.
- Locate the part: check the indoor air filter and both coils for dirt or ice before any reset; the cut-out is on the suction side inside the outdoor unit
- Test: a technician with gauges must confirm whether suction pressure is genuinely collapsing or the switch opens at normal pressure; the manual's test point reads 0V AC across the cut-out when closed and 24V AC when open on related controls, separating switch state from pressure guesswork
- End point: fix airflow causes yourself. True low pressure means leak repair and charging by an EPA-certified technician; do not keep cycling power out of the hard lockout to force the compressor to run. Any work that opens the sealed refrigerant circuit, adjusts charge, or replaces a refrigerant pressure device is EPA-certified technician work only.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Air filter.
Also tied to this fault: Control board - Shop at Amazon
Parts that commonly fix it
- Air filter$5–$30Shop at Amazon
- Control boardShop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related American Standard Heat pump 4A7A6048C1000B heat pump with AccuLink and Charge Assist problems
- ERR 90
- 1 flash
- 10 flashes
- 11 flashes
- 12 flashes
- 13 flashes
- 14 flashes
- 17 flashes
- 18 flashes
- 2 flashes
- 3 flashes
- 4 flashes
See all American Standard 4A7A6048C1000B heat pump with AccuLink and Charge Assist codes & guides →