American Standard Heat pump 4A7A6048C1000B heat pump with AccuLink and Charge Assist 12 flashes

What it should look like on your machine

then it repeats

12 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Read on the red Fault LED of the AccuLink outdoor control, and shown at the comfort control as ERR 113. The Summary of Alert Code and Charge Assist LEDs in the American Standard Service Facts lists twelve flashes as a liquid pressure sensor fault, out of range - open or shorted. The liquid pressure transducer gives the outdoor control actual liquid-line pressure, which Charge Assist uses to judge charge - the manual notes liquid pressure must be above 90 PSIG to enter Charge Assist mode. It matters because without trustworthy pressure data the control cannot run its charging or pressure-monitoring functions.

Likely causes

  1. Liquid pressure sensor (transducer) open or shorted or out of range
  2. Damaged transducer wiring or connector at the outdoor control board
  3. Transducer port blocked or transducer not properly fitted to the liquid line
  4. Failed sensor input on the outdoor control board

How to fix it — step by step

  1. Record the code before cycling power: count twelve flashes and record ERR 113 before cycling power. Power-cycling can clear, change or recount the fault, so note the display, operating mode and outdoor temperature first.
  2. Safety: turn the system off, open the outdoor disconnect and breaker, verify with a meter that the unit is dead before touching wiring, and stay clear of the run capacitor terminals - a capacitor can hold a shock charge with power off.
  3. Locate the part: locate the liquid pressure transducer on the liquid line at the outdoor unit and its harness back to the outdoor control board in the control box
  4. Test: inspect the harness and connector first; confirming a transducer's output against actual liquid pressure requires gauges on the sealed system, which is technician work - do not remove the transducer, it is on a pressurised refrigerant line
  5. End point: a technician who verifies normal liquid pressure while the sensor reports out of range replaces the transducer or repairs its harness; a proven-good transducer that still faults condemns the outdoor control board. Any work that opens the sealed refrigerant circuit, adjusts charge, or replaces a refrigerant pressure device is EPA-certified technician work only. → Shop the control board at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related American Standard Heat pump 4A7A6048C1000B heat pump with AccuLink and Charge Assist problems

See all American Standard 4A7A6048C1000B heat pump with AccuLink and Charge Assist codes & guides →