Slant/Fin Boiler Prodigy 21 (KC-50/KC-100) 5 flashes

What it should look like on your machine

then it repeats

5 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Five flashes means blower RPM too low. The manual's causes are motor wiring faults (particularly the cable to the RPM control on the motor shaft), a restricted blower wheel, a blower motor not running, and a defective blower optical board that reads the wheel's rotation.

Likely causes

  1. Blower motor wiring fault, especially the RPM control cable
  2. Blower wheel restricted by foreign material or misalignment
  3. Blower motor not running
  4. Defective blower optical board

How to fix it — step by step

  1. Record the code before resetting anything: write down the display exactly as shown (5 flashes) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
  2. Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
  3. Locate the part: the blower/motor assembly is at the top of the boiler behind the air filter box; the electronic board carries a Blower RPM indicator LED that reads the optical sensor.
  4. Test: check the motor wiring, then reach through the filter box and confirm the wheel turns freely. Set the operation selector to CAL; the motor should run. For the optical board test, disconnect the motor connector and spin the wheel by hand: the Blower RPM LED should blink with each revolution. No blinking condemns the optical board path.
  5. End at the pinpoint: clear the restriction or replace the Blower/motor assembly (same manufacturer and model), or replace the Control board if the optical reading is dead, as the tests condemn. Technician work. → Shop the control board at Amazon → Shop the blower motor at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.