Slant/Fin Boiler Prodigy 21 (KC-50/KC-100) 3 flashes
What it should look like on your machine
then it repeats
3 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Three flashes means a pressure switch problem. The control cannot prove correct airflow for combustion. The manual's causes are wiring faults, no pressure signal reaching the switch (loose or blocked tubing, loose blower hose or wheel, blocked air filter, vent terminal, or vent tubing), incorrect blower speed, and a defective pressure switch.
Likely causes
- Pressure switch wiring fault
- Loose or blocked tubing to the pressure switch
- Loose blower hose connection or blower wheel
- Blocked air filter, vent terminal, or vent tubing
- Blower speed not correct
- Defective pressure switch
How to fix it — step by step
- Record the code before resetting anything: write down the display exactly as shown (3 flashes) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
- Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
- Locate the part: the pressure switch is by the blower, with clear tubing running to its sensing points; wires land on the switch's Normally Open and Common terminals.
- Test: check the wiring to the N.O. and C terminals, secure every tubing and blower hose connection, tighten the blower wheel set screw, and clear the filter and vent path. Then check the switch itself per the manual: its contacts must be open (between N.O. and C) when the blower is off, and its calibration is checked as shown in the manual's How To Do It section.
- End at the pinpoint: correct the wiring/tubing/blockage found, recalibrate blower speed, or replace the Pressure switch (same manufacturer, model, and calibration, tubing orientation observed) as condemned. Technician work. → Shop the pressure switch at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Pressure switch.
Shop the Pressure switch at Amazon
Also tied to this fault: Blower - Shop at Amazon
Parts that commonly fix it
- Pressure switch$50–$205Shop at Amazon
- BlowerShop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Slant/Fin Boiler Prodigy 21 (KC-50/KC-100) problems
- 4 flashes
- 5 flashes
- 6 flashes
- 7 flashes
- Continuous flashing (diagnostic LED)
- Steady on
- 1 flash
- 2 flashes
See all Slant/Fin Prodigy 21 (KC-50/KC-100) codes & guides →