Rheem Furnace Seven-segment display — R95P platform 22 Error Code
What the 22 code means
Main limit open on Rheem furnaces with the 7-segment diagnostic display. The main limit safety opened from overheating, most often from restricted airflow; if it stays open over 150 seconds the control also flags a blower fault.
Likely causes
- dirty air filter
- closed registers or blocked returns
- blower failure
- restricted ductwork
How to fix it — step by step
- Turn the thermostat down and let the furnace cool
- Replace the air filter if it is dirty or clogged
- Open all supply registers and make sure return vents are not blocked by furniture
- Restore the heat call and watch whether the code returns
- If the limit code repeats, stop and call a licensed HVAC technician
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the limit switch.
Shop the limit switch at RepairClinic or Amazon
Also tied to this fault: blower motor - Shop at RepairClinic or Amazon
Parts that commonly fix the 22 code
- limit switch - Shop at RepairClinic or Amazon
- blower motor - Shop at RepairClinic or Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number inside the blower/burner compartment door. It's the key to the right manual pages and the right parts.
Related Rheem Furnace Seven-segment display — R95P platform error codes
See all Rheem Seven-segment display — R95P platform codes & guides →