Peerless Pinnacle (PI / PI-T) series, PI25 control Error Codes

Find your code in the list below. Each page explains what the code means, the most likely causes, step-by-step fixes you can do yourself, and the parts that commonly resolve it. 18 codes covered.

Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.

CodeWhat it meansCheck first
E00A temporary error code: high limit exceeded, shown for 50 seconds before it escalates. The boiler water has…Circulation pump not operating correctly›
E13A temporary error code: combustion fan speed low. The boiler combustion air fan is running at less than 70…Combustion air fan wiring fault›
E14A temporary error code: combustion fan speed high. The boiler combustion air fan is running at more than 130…Combustion air fan wiring fault›
F00A fault lockout: high limit exceeded. The boiler overheated and locked out, and the red fault light is on…Circulation pump not operating correctly›
F01A fault lockout: vent temperature limit exceeded. The vent temperature limit switch has tripped on excessive…Vent temperature genuinely too high during operation›
F02A fault lockout: the supply (outlet) thermistor is interrupted or shorted. The control has lost the boiler's…Loose or failed electrical connection to the thermistor on the outlet manifold›
F03A fault lockout: the return (inlet) thermistor is interrupted or shorted. Without a valid inlet temperature…Loose or failed electrical connection to the thermistor on the inlet manifold›
F05A fault lockout: the supply (outlet) temperature exceeded 230 degrees F. That is well past normal operating…Circulation pump not operating›
F06A fault lockout: the return (inlet) temperature exceeded 230 degrees F. Return water that hot is abnormal in…Circulation pump not operating correctly›
F09A fault lockout: no flame detected. The boiler made three attempts at ignition before the control locked out…Spark electrode gap wrong, not the proper 1/4 inch›
F10A fault lockout: loss of flame signal. The boiler lit, then lost its flame signal, relit four times, and…Gas pressure to the gas valve low or unstable during operation›
F11A fault lockout: false flame signal. The control senses a flame signal when there should be none present, and…Flame rod faulty, reporting a signal with no flame›
F13A fault lockout: combustion fan speed low. The control sensed the fan speed at less than 70 percent of…Combustion air fan wiring fault›
F14A fault lockout: combustion fan speed high. The control sensed the fan speed at more than 130 percent of…Combustion air fan wiring fault›
F18A fault lockout: gas valve error. The control has detected a fault in the gas valve circuit, and the…Gas valve connector not correctly connected›
FLuAn error display, not a numbered code: the blocked vent pressure switch is open, and it stays displayed until…Blocked vent or flue passage›
NCA fault display: neutral fault. The boiler locks out if it senses a voltage drop or power feedback on the…Inadequate supply voltage to the boiler›
PROAn error display, not a numbered code: the water pressure switch is open, and it stays displayed until…System pressure at or below 10 psig›