Peerless Boiler Pinnacle (PI / PI-T) series, PI25 control E13 Error Code
What the E13 code means
A temporary error code: combustion fan speed low. The boiler combustion air fan is running at less than 70 percent of its expected speed, and the error shows for 60 seconds before escalating toward the F13 lockout if it is not corrected. A fan that cannot move enough air cannot support safe combustion.
Likely causes
- Combustion air fan wiring fault
- Failing combustion air fan
- Failing control board
How to fix it — step by step
- Record the code exactly as shown, E13, and the fan speed from status menu value d3, shown in hundreds of rpm.
- Safety: switch off all electrical power and close the gas supply before opening the boiler or handling fan wiring.
- Locate the combustion air fan inside the boiler cabinet and follow its wiring back to the control board, checking each connection.
- Test: a fan that runs slowly or not at all on sound wiring has failed. A fan that runs correctly while the control still reports low speed points at the control board's speed sensing. → Shop the control board at Amazon
- End at the fix: repair the fan wiring if it is at fault, replace the combustion air fan if it cannot reach speed, and replace the control board only if a good fan still reports wrong. Work through them in that order.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Combustion air fan.
Shop the Combustion air fan at Amazon
Also tied to this fault: Control board - Shop at Amazon
Parts that commonly fix the E13 code
- Combustion air fanShop at Amazon
- Control boardShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Peerless Boiler Pinnacle (PI / PI-T) series, PI25 control error codes