Peerless Boiler Pinnacle (PI / PI-T) series, PI25 control E00 Error Code
What the E00 code means
A temporary error code: high limit exceeded, shown for 50 seconds before it escalates. The boiler water has gone over the high limit, which almost always means water is not moving heat away from the boiler fast enough. If the condition is not corrected, the control moves on to the F00 fault lockout.
Likely causes
- Circulation pump not operating correctly
- Inadequate flow through the boiler, with more than a 50 degree F rise from return to supply
- Faulty high limit switch
How to fix it — step by step
- Record the code exactly as shown, E00, and note the supply and return temperatures from the status menu.
- Safety: if the boiler is overheating, shut off the gas supply at the gas service valve rather than cutting power to the circulating pump, which can make overheating worse.
- Locate the boiler circulator and confirm it runs on a call for heat, then read the status menu values d1 (supply) and d2 (return).
- Test: a rise from return to supply of less than 50 degrees F is adequate flow. A wider rise confirms the flow problem. Normal temperatures with the code still setting point at the high limit switch. → Shop the high limit switch at Amazon
- End at the fix: restore circulation and adequate flow through the boiler. If flow and temperatures are correct, replace the high limit switch.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the High limit switch.
Shop the High limit switch at Amazon
Also tied to this fault: Circulator - Shop at Amazon
Parts that commonly fix the E00 code
- High limit switchShop at Amazon
- CirculatorShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.