Peerless Boiler Error Codes
Find your code in the list below. Each page explains what the code means, the most likely causes, step-by-step fixes you can do yourself, and the parts that commonly resolve it. 18 codes covered.
Finding your model number: it is on the rating plate on the boiler jacket, often behind the front panel.
Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.
Pinnacle with PI25 control (E errors + F faults)
The PI25 control reports two lists: E-codes are its error table and F-codes its fault table. The status menu shows d1 supply, d2 return, d3 fan speed and d4 flame signal in microamps - the numbers the fault checks use.
| Code | What it means | Check first | |
|---|---|---|---|
| E00 | A temporary error code: high limit exceeded, shown for 50 seconds before it escalates. The boiler water has… | Circulation pump not operating correctly | › |
| E13 | A temporary error code: combustion fan speed low. The boiler combustion air fan is running at less than 70… | Combustion air fan wiring fault | › |
| E14 | A temporary error code: combustion fan speed high. The boiler combustion air fan is running at more than 130… | Combustion air fan wiring fault | › |
| F00 | A fault lockout: high limit exceeded. The boiler overheated and locked out, and the red fault light is on… | Circulation pump not operating correctly | › |
| F01 | A fault lockout: vent temperature limit exceeded. The vent temperature limit switch has tripped on excessive… | Vent temperature genuinely too high during operation | › |
| F02 | A fault lockout: the supply (outlet) thermistor is interrupted or shorted. The control has lost the boiler's… | Loose or failed electrical connection to the thermistor on the outlet manifold | › |
| F03 | A fault lockout: the return (inlet) thermistor is interrupted or shorted. Without a valid inlet temperature… | Loose or failed electrical connection to the thermistor on the inlet manifold | › |
| F05 | A fault lockout: the supply (outlet) temperature exceeded 230 degrees F. That is well past normal operating… | Circulation pump not operating | › |
| F06 | A fault lockout: the return (inlet) temperature exceeded 230 degrees F. Return water that hot is abnormal in… | Circulation pump not operating correctly | › |
| F09 | A fault lockout: no flame detected. The boiler made three attempts at ignition before the control locked out… | Spark electrode gap wrong, not the proper 1/4 inch | › |
| F10 | A fault lockout: loss of flame signal. The boiler lit, then lost its flame signal, relit four times, and… | Gas pressure to the gas valve low or unstable during operation | › |
| F11 | A fault lockout: false flame signal. The control senses a flame signal when there should be none present, and… | Flame rod faulty, reporting a signal with no flame | › |
| F13 | A fault lockout: combustion fan speed low. The control sensed the fan speed at less than 70 percent of… | Combustion air fan wiring fault | › |
| F14 | A fault lockout: combustion fan speed high. The control sensed the fan speed at more than 130 percent of… | Combustion air fan wiring fault | › |
| F18 | A fault lockout: gas valve error. The control has detected a fault in the gas valve circuit, and the… | Gas valve connector not correctly connected | › |
| FLu | An error display, not a numbered code: the blocked vent pressure switch is open, and it stays displayed until… | Blocked vent or flue passage | › |
| NC | A fault display: neutral fault. The boiler locks out if it senses a voltage drop or power feedback on the… | Inadequate supply voltage to the boiler | › |
| PRO | An error display, not a numbered code: the water pressure switch is open, and it stays displayed until… | System pressure at or below 10 psig | › |
Common questions
What does F09 mean on a Peerless Pinnacle?
No flame detected: the control made three ignition attempts without proving flame. The manual's checks are to watch the igniter through the observation window, check the 1/4-inch spark gap and corrosion, and confirm the gas supply and flame sensor.
What is the difference between Peerless E-codes and F-codes?
Both come from the PI25 control's troubleshooting tables: the E list is its error table (E00 high limit, E13/E14 fan speed out of range) and the F list its fault table (F00-F18). Some conditions appear in both - high limit is E00 in one table and F00 in the other.
Once you know the part you need, browse Peerless Boiler replacement parts → The parts shelves are organized by brand, with the parts that actually fix these codes.