Peerless Boiler Pinnacle (PI / PI-T) series, PI25 control E14 Error Code

What the E14 code means

A temporary error code: combustion fan speed high. The boiler combustion air fan is running at more than 130 percent of its expected speed, shown for 60 seconds before escalating toward the F14 lockout if uncorrected. Overspeed is a control or fan fault, not an airflow blockage.

Likely causes

  1. Combustion air fan wiring fault
  2. Failing combustion air fan
  3. Failing control board

How to fix it — step by step

  1. Record the code exactly as shown, E14, and the fan speed from status menu value d3.
  2. Safety: switch off all electrical power and close the gas supply before opening the boiler.
  3. Locate the combustion air fan and check its wiring to the control board for shorts, crossed connections or damage.
  4. Test: a fan that overspeeds on correctly wired connections is failing internally or being driven wrong. Swapping the test order matters: wiring first, then the fan, then the board, because the board is condemned only after the fan and wiring prove good.
  5. End at the fix: repair the fan wiring if faulty, replace the combustion air fan if it overspeeds on good wiring, and replace the control board if a known good fan still overspeeds. → Shop the combustion air fan at Amazon → Shop the control board at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the E14 code

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Peerless Boiler Pinnacle (PI / PI-T) series, PI25 control error codes

See all Peerless Pinnacle (PI / PI-T) series, PI25 control codes & guides →