Goodman Furnace GMES96 — LED flash-count control 6 flashes

What it should look like on your machine

then it repeats

6 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Open rollout temperature limit switch on Goodman GMES96-series furnaces. The rollout safety tripped, meaning flame escaped the burner compartment — a stop-and-call fault, not a reset-and-see fault.

Likely causes

  1. flame rollout from the burners
  2. blocked flue or vent
  3. failed inducer motor
  4. cracked heat exchanger

How to fix it — step by step

  1. Turn the furnace off at the power switch and close the manual gas shutoff if you can do so safely
  2. Do not reset the rollout switch yourself → Shop the rollout switch at RepairClinic
  3. If anyone has headache or nausea or a CO alarm sounds, leave the building and call from outside
  4. Call a licensed HVAC technician to inspect the burners and heat exchanger → Shop the heat exchanger at RepairClinic

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.