Viessmann Boiler Vitodens 100-W 30 Error Code

What the 30 code means

Fault 30 blocks the burner because the boiler water temperature sensor is short circuited. The control cannot trust the boiler temperature reading, so it shuts the burner down for safety. This is a sensor or sensor wiring fault, not an overheating event.

Likely causes

  1. Short circuit in the boiler water temperature sensor
  2. Shorted sensor lead

How to fix it — step by step

  1. Record the code before resetting: write down fault code 30 exactly as shown on the Vitodens 100-W display, and note whether the display calls the burner blocked or in a fault state.
  2. Safety: turn the boiler off at its ON/OFF switch and isolate power before removing the front cover or touching sensor wiring. Do not work on the gas train, burner or flue unless you are a qualified heating contractor.
  3. Locate the part: the boiler water temperature sensor is fitted in the boiler, sensing boiler water temperature, and is wired to the control unit where fault 30 is displayed.
  4. Test: check the boiler water temperature sensor and its lead for a short circuit. A short that stays with the sensor unplugged is in the lead; a short across the sensor itself condemns the sensor.
  5. End at the fix: correct the pinpointed cause, then press Reset by tapping and holding R for about 2 seconds. If 30 returns straight away, the pinpointed part is the cause and needs replacement by a contractor.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 30 code

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.