Ruud Furnace 801S Series (7 segment display control) 57 Error Code

What the 57 code means

Pressure switch stuck open when it should be closed. The inducer runs but the switch never proves draft, so ignition cannot start.

Likely causes

  1. Blocked vent or intake pipe
  2. Pressure switch hose off, cracked, or plugged
  3. Weak induced draft blower
  4. Failed pressure switch

How to fix it — step by step

  1. Turn the power off before opening any panel.
  2. Find the pressure switch by the inducer and inspect its rubber hose end to end. Reconnect or replace a hose that is off, cracked, or plugged, and clear the inducer port.
  3. Check the vent and intake terminations outside for snow, nests, or debris.
  4. Restore power and call for heat. The inducer should start at once. An inducer that does not run is the fault, not the switch.
  5. If the inducer runs strong and the vent is clear, test the switch during the run. No closure means the switch failed. A five minute soft lockout follows if the switch never closes in the proving period.
  6. Replace the switch with the correct setpoint part. Weak draft with a good switch means inducer or vent work, which is pro work.
  7. Verify after the repair: restore power and run a full heat call from the thermostat and watch one complete heating cycle - ignition, steady burn and shutoff - 57 should stay clear for the whole cycle. If it comes back, the repair did not cure it: hand over the point in the sequence where it reappears, because that timing is the diagnosis

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 57 code

Parts run $50–$205Typical pro repair $133–$505

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number inside the blower/burner compartment door. It's the key to the right manual pages and the right parts.

Related Ruud Furnace 801S Series (7 segment display control) error codes

See all Ruud 801S Series (7 segment display control) codes & guides →