Rinnai Water heater 33 Error Code
What the 33 code means
Heat exchanger thermistor fault. The heat exchanger outlet temperature sensor signal is faulty.
Likely causes
- Thermistor wiring loose, broken or damaged
- Scale build-up on the thermistor
- Failed heat exchanger thermistor
How to fix it — step by step
- Check the thermistor wiring harness for loose, broken or damaged connections from the thermistor back to the PC Board
- Turn off the water supply and drain the system, remove the thermistor and clean any scale build-up off it
- Test resistance with a meter on the 20K ohm scale: 11.4-14K ohms at 59 F, 6.4-7.8K at 86 F, 3.6-4.5K at 113 F, 2.2-2.7K at 140 F - resistance should fall as the bulb warms in your fingers
- Reinstall with its O-ring intact and a little grease on the O-ring, turn the water on, check for leaks and re-fire the heater
- If code 33 still appears after cleaning and testing, replace the heat exchanger thermistor → Shop the heat exchanger thermistor at Amazon
- Verify after the repair: restore gas, water and power, then open a hot tap and let the heater fire and run for several minutes - 33 should stay clear through the whole draw. If it comes back, the repair did not cure it: hand over the point in the sequence where it reappears, because that timing is the diagnosis
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Heat exchanger thermistor.
Parts that commonly fix the 33 code
- Heat exchanger thermistor$300–$900Shop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
Before you buy: check the heat exchanger thermistor first
Test: Power disconnected and the sensor isolated: insert the meter leads into each end of the thermistor plug, meter on the 20K scale (Rinnai Electrical Diagnostics).
A good one reads: 11.4-14 kΩ at 59 °F; 6.4-7.8 kΩ at 86 °F; 3.6-4.5 kΩ at 113 °F; 2.2-2.7 kΩ at 140 °F. Warming the bulb must lower the reading and icing it must raise it; a fixed or open reading condemns the sensor.
Test values from images.tradeservice.com documentation - confirm against your model's own tech sheet.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.