Kohler Generator 14/20RESA, 14/20RESAL (RDC2/DC2 controller) Generator Frequency Low

What this problem usually means

Governed frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below the system frequency setting for more than 60 seconds. The function becomes active 10 seconds after engine start.

Likely causes

  1. Load too heavy, dragging frequency down
  2. Engine governing or fuel fault

How to fix it — step by step

  1. Reduce the load and restart the generator set. Frequency is tied to engine speed, so a set that recovers on a lighter load was overloaded.
  2. Test again with normal household loads restored in stages. Frequency holding through the staged test is the completed fix.
  3. If frequency still falls on a light load, the pinpoint is governing or fuel delivery. Book dealer service and report Generator Frequency Low.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

This fault usually does not need a replacement part - the fix is in the steps above. If your generator does need a part, start with the link above.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.