Kohler Generator Common Problems
Find your problem in the list below. Each page explains the most likely causes, step-by-step checks you can do yourself, when to call a pro, and the parts that commonly resolve it. 15 problems covered.
Finding your model number: it is on the unit's rating plate.
Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.
14/20RESA, 14/20RESAL (RDC2/DC2 controller)
| Problem | What it means | Check first | |
|---|---|---|---|
| AC Sens Lost | AC sensing is lost. Detection starts 10 seconds after crank disconnect. It is a warning after 1 second if no… | Generator output AC sensing lost | › |
| ATS Com Error | ATS communication error. The warning is displayed if the connection to the transfer switch interface board is… | Communication wiring between the transfer switch interface board and the generator set | › |
| Battery Voltage High | Engine starting battery voltage has risen above 16 VDC for more than 10 seconds. The check is inhibited… | Battery charger overcharging | › |
| Battery Voltage Low | Engine starting battery voltage has fallen below 12.5 VDC for more than 90 seconds while the engine is not… | Battery discharged or failing | › |
| Engine Oil Pressure Low | The low oil pressure switch indicates low oil pressure for more than 5 seconds. The function becomes active… | Oil level low | › |
| EngineSpeed High | Engine speed exceeds 115% of normal running speed for more than 0.3 seconds and the set shuts down. Overspeed… | Engine governing fault driving speed above 115% of normal | › |
| EngineSpeed Low | Engine speed drops below 85% of normal running speed for more than 3 seconds and the set shuts down. An… | Load on the generator set too heavy for the engine to hold speed | › |
| Fails Exercise | The exercise cycle does not run as expected. Two controller states cover this symptom: Exer Not Sch, a… | No exercise scheduled on the controller | › |
| Generator Frequency Low | Governed frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below… | Load too heavy, dragging frequency down | › |
| Generator Voltage L1-L2 Low | Generator output voltage falls below 80% of the nominal system voltage for more than 10 seconds and the set… | Load too heavy for the set | › |
| Lo Crank Vlt | Low cranking voltage. Battery voltage falls below 8 VDC for more than 6 seconds while the starter is engaged… | Weak or discharged battery that cannot hold voltage under starter load | › |
| Locked Rotor | No engine rotation is sensed during cranking. The set shuts down 3 seconds after the fault is detected. The… | Battery too weak to turn the engine over | › |
| Over Crank | Three unsuccessful starting attempts. The engine cranked but never started, and the controller stopped trying… | Fuel supply off, empty or interrupted | › |
| Won't Start | The engine cranks, or tries to, and does not start. On this controller family the starting faults report as… | Fuel supply off or empty | › |
| Won't Turn On | The set does not respond, does not start on a power failure, or sits idle when it should be in standby. Work… | Controller not in Automatic mode (Not in Auto warning) | › |