Kohler Generator 14/20RESA, 14/20RESAL (RDC2/DC2 controller) Engine Oil Pressure Low
What this problem usually means
The low oil pressure switch indicates low oil pressure for more than 5 seconds. The function becomes active 30 seconds after crank disconnect. This shutdown does not protect against low oil level, so the oil level still has to be checked on its own schedule.
Likely causes
- Oil level low
- Leak in the lubrication system
- Low oil pressure with the level correct
How to fix it — step by step
- Stop and let the engine cool. Pull the dipstick at the engine, access inside the enclosure, and read the oil level. Low on the stick is the first branch.
- Check for leaks in the lubrication system: oil under the set, a wet filter or a loose drain points to where the oil went. Add oil to the correct level if it is low and no leak is active.
- Reset the controller only after the cause is corrected, then run the set and watch the message. Oil pressure holding with no shutdown is the fix. Level correct, no leak, and the shutdown returns means true low pressure inside the engine. Do not keep running it. That is dealer service.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the Engine oil.
Also tied to this fault: Oil filter - Shop at Amazon
Parts that commonly fix it
- Engine oilShop at Amazon
- Oil filter$5–$15Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.
Related Kohler Generator 14/20RESA, 14/20RESAL (RDC2/DC2 controller) problems
- EngineSpeed High
- EngineSpeed Low
- Fails Exercise
- Generator Frequency Low
- Generator Voltage L1-L2 Low
- Lo Crank Vlt
- Locked Rotor
- Over Crank
- Won't Start
- Won't Turn On
- AC Sens Lost
- ATS Com Error
See all Kohler 14/20RESA, 14/20RESAL (RDC2/DC2 controller) codes & guides →