Kohler Generator 14/20RESA, 14/20RESAL (RDC2/DC2 controller) Lo Crank Vlt

What this problem usually means

Low cranking voltage. Battery voltage falls below 8 VDC for more than 6 seconds while the starter is engaged, so the battery collapses under cranking load even if it looked acceptable at rest.

Likely causes

  1. Weak or discharged battery that cannot hold voltage under starter load
  2. Loose or corroded battery connections

How to fix it — step by step

  1. Start at the starting battery inside the enclosure. Clean and tighten both cable connections first, since a loose connection drops voltage exactly when the starter pulls hard.
  2. Charge the battery fully and try one start. Strong cranking with no Lo Crank Vlt warning means the battery was simply discharged and the fix is complete.
  3. If a fully charged battery still drops out during cranking, the battery has failed under load. Replace it. A new battery that also sags points to the starter circuit, which is dealer service. → Shop the battery at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $50–$150

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.

Related Kohler Generator 14/20RESA, 14/20RESAL (RDC2/DC2 controller) problems

See all Kohler 14/20RESA, 14/20RESAL (RDC2/DC2 controller) codes & guides →