Kohler Generator 14/20RESA, 14/20RESAL (RDC2/DC2 controller) Won't Start

What this problem usually means

The engine cranks, or tries to, and does not start. On this controller family the starting faults report as Over Crank after three unsuccessful attempts, Locked Rotor when no rotation is sensed, and Lo Crank Vlt when the battery collapses under the starter. Carbon monoxide warning: run and test this generator outdoors only, never indoors or in a garage, with exhaust away from windows, doors and vents.

Likely causes

  1. Fuel supply off or empty
  2. Spark plug fouled
  3. Battery weak, discharged or loose connections
  4. No engine rotation during cranking (Locked Rotor)

How to fix it — step by step

  1. Read the controller display before resetting anything. The fault message shown is the branch selector: Over Crank, Locked Rotor and Lo Crank Vlt each send you to a different first check.
  2. Fuel branch: confirm the fuel valve is open and the propane supply is not empty. Battery branch: check charge and tighten the cable connections at the battery inside the enclosure. Plug branch: pull and inspect the spark plug, and replace a fouled plug.
  3. Correct the branch the message names, reset the controller by pressing OFF, then press AUTO and make one start attempt. A clean start with no returning fault is the fix.
  4. If the set still fails with fuel, plug, battery and connections proven, the fault is inside the fuel or ignition system. Stop and book dealer service, reporting the exact fault message displayed.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $5–$150

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.

Related Kohler Generator 14/20RESA, 14/20RESAL (RDC2/DC2 controller) problems

See all Kohler 14/20RESA, 14/20RESAL (RDC2/DC2 controller) codes & guides →