Heil Furnace N9MP (ICP) 8 flashes

What it should look like on your machine

then it repeats

8 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Permanent lockout. The gas valve relay contact is stuck closed, or the gas valve is miswired. Only a power reset clears it, after the cause is fixed.

Likely causes

  1. Gas valve relay contact on the control stuck closed
  2. Gas valve miswired so it receives power out of sequence

How to fix it — step by step

  1. Turn the power off and close the gas shutoff at once. This lockout means the control thinks the gas valve can be powered when it should not be.
  2. If you smell gas, leave and call the gas supplier from outside.
  3. This lockout clears only with a power reset, and only after the wiring or control fault is repaired.
  4. Check the gas valve wiring against the wiring diagram for crossed or wrongly landed wires if any recent work was done.
  5. In most cases the fix is a new furnace control board, since the relay is part of the board. That is pro work.
  6. Verify the fix: restore power and run a full heat call from the thermostat and watch one complete heating cycle - ignition, steady burn and shutoff - the furnace should complete the cycle with no code returning. If it comes back, the fault is still present: recheck the step above whose result was borderline, and treat the part that step points to as the one to replace

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Typical pro repair $200–$600

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.