Heil Furnace N9MP (ICP) 4 flashes

What it should look like on your machine

then it repeats

4 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Limit or rollout switch open for less than 2 minutes. A safety switch in the limit circuit opened, most often because the furnace overheated from low airflow.

Likely causes

  1. Dirty filter or restricted ducts overheating the furnace
  2. Loose blower wheel moving too little air
  3. Defective blower motor
  4. Restricted or undersized vent or inadequate combustion air
  5. Defective limit or rollout switch or a bad connection

How to fix it — step by step

  1. Leave the power on at first. On this fault the blower runs for 4 minutes or until the open switch remakes, whichever is longer. Let it cool the furnace.
  2. Turn the power off and replace a dirty air filter, then open closed registers and clear the returns.
  3. Check the blower wheel. Remove the blower door, spin the wheel by hand, and check the set screw on the motor shaft. A loose wheel slips and moves almost no air.
  4. Restore power and call for heat. Confirm the blower runs at full speed. A weak or dead blower motor explains the trip.
  5. If airflow is good, turn the power off and test the limit and rollout switches with a meter when cool. One that reads open when cold has failed, unless it is the rollout switch reporting a real event, in which case check the vent and combustion air before resetting anything. → Shop the rollout switch at Amazon → Shop the limit switch at Amazon
  6. Replace a switch only after the airflow or vent cause is fixed. Repeated trips need a pro.
  7. Verify the fix: restore power and run a full heat call from the thermostat and watch one complete heating cycle - ignition, steady burn and shutoff - the furnace should complete the cycle with no code returning. If it comes back, the fault is still present: recheck the step above whose result was borderline, and treat the part that step points to as the one to replace

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $5–$450Typical pro repair $150–$2,000

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number inside the blower/burner compartment door. It's the key to the right manual pages and the right parts.

Related Heil Furnace N9MP (ICP) problems

See all Heil N9MP (ICP) codes & guides →