Slant/Fin Boiler Victory VSPH series PRES SWITCH LED flashing
What this problem usually means
A flashing PRES SWITCH LED by itself means the pressure switch opened during the boiler run period. The boiler proved airflow at startup and then lost it mid-run. The manual's remedy is to check the pressure switch and its hoses and check for obstruction in the venting, air intake piping, and termination, and it notes wind gusts over 40 mph can trip it.
Likely causes
- Pressure switch opened during the run
- Loose or damaged pressure switch hoses
- Obstruction in venting or air intake piping/termination
- Wind gusts over 40 mph at the termination
- Defective pressure switch
How to fix it — step by step
- Record the code before resetting anything: write down the display exactly as shown (PRES SWITCH LED flashing) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
- Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
- Locate the part: the pressure switch and its plastic hoses by the inducer; the vent and air intake runs and their outside termination.
- Test: inspect and reseat the hoses, then inspect the full vent and intake path for a partial blockage that only bites at full flow. A clear path with sound hoses and repeat trips in calm weather condemns the pressure switch.
- End at the pinpoint: clear the obstruction, replace damaged hoses, or replace the Pressure switch (do not adjust it) as condemned. Technician work. → Shop the pressure switch at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Pressure switch.
Shop the Pressure switch at Amazon
Also tied to this fault: Inducer motor - Shop at Amazon
Parts that commonly fix it
- Pressure switch$50–$205Shop at Amazon
- Inducer motorShop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.