Slant/Fin Boiler Victory VSPH series FLAME LED flashing

What this problem usually means

A flashing FLAME LED by itself is a control lockout: the pilot flame was not established during the trial for ignition. The manual's remedy list is to check the gas valve knob is in the ON position, check inlet gas pressure, check the pilot gas line, check the ignition cable and its connections, and check that the pilot flame is 3/8 to 1/2 inch long.

Likely causes

  1. Pilot flame not established during trial for ignition
  2. Gas valve knob not in the ON position
  3. Low inlet gas pressure
  4. Blocked or leaking pilot gas line
  5. Ignition cable or connection fault
  6. Pilot flame too short (under 3/8 inch)

How to fix it — step by step

  1. Record the code before resetting anything: write down the display exactly as shown (FLAME LED flashing) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
  2. Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
  3. Locate the part: the pilot assembly and its gas line are at the burner behind the air box front panel; the ignition cable runs from the pilot to the integrated boiler control; the gas valve knob is on the gas valve in the front gas train.
  4. Test: work the manual's list in order: knob ON, inlet pressure at the valve, pilot line clear, ignition cable seated and undamaged, then observe the pilot flame length against the 3/8 to 1/2 inch specification. Each check that fails is a cause found; all passing with no pilot established condemns the gas valve or control output.
  5. End at the pinpoint: correct the gas supply or pilot line, repair the Ignition cable, or replace the Pilot assembly or Gas valve as the checks condemn, then reset with a 45-second power-off. Technician work. → Shop the pilot assembly at Amazon → Shop the gas valve at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $100–$355

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Slant/Fin Boiler Victory VSPH series problems