Slant/Fin Boiler Victory VSPH series POWER + PRES SWITCH LEDs flashing
What this problem usually means
Flashing POWER and PRESS SWITCH LEDs together is a control lockout: the pressure switch contacts are closed before the blower is energized, or they do not close within 5 minutes of the blower turning on. The manual's remedy path is to check the air pressure switch, check the hose connections to the switch, and check for obstruction or restriction in the venting, air intake piping, and termination.
Likely causes
- Pressure switch contacts closed before the blower starts
- Pressure switch does not close within 5 minutes of blower start
- Blocked or restricted venting or air intake
- Defective pressure switch
How to fix it — step by step
- Record the code before resetting anything: write down the display exactly as shown (POWER + PRES SWITCH LEDs flashing) and whether the boiler was in a heating call, a hot-water call, or idle when it appeared.
- Safety: turn the thermostat down, switch off power to the boiler at the service switch and breaker, and close the manual gas shutoff if you smell gas or see scorching. Do not open the burner compartment if you smell gas; leave and call the gas supplier.
- Locate the part: the pressure (air flow proving) switch is by the inducer/blower, with plastic hoses running to its sensing points; the vent and air intake piping run from the boiler to their termination.
- Test: with the blower off, the switch contacts should be open; contacts closed at rest condemn the switch. With the blower running, check the hoses are connected and clear and inspect the vent and intake path and termination for obstruction before condemning the switch.
- End at the pinpoint: clear the vent/intake obstruction, reconnect or replace the hoses, or replace the Pressure switch (do not adjust it, per the manual) as the checks condemn, then reset the lockout with a 45-second power-off. Technician work. → Shop the pressure switch at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Pressure switch.
Shop the Pressure switch at Amazon
Also tied to this fault: Inducer motor - Shop at Amazon
Parts that commonly fix it
- Pressure switch$50–$205Shop at Amazon
- Inducer motorShop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.