Rheem Heat pump RP20 variable-speed heat pumps with Variable Speed Outdoor Control (VSODC) and EcoNet d1 Error Code

What the d1 code means

Read as d1 on the dual 7-segment LED of the Variable Speed Outdoor Control in the outdoor unit, and as EcoNet fault A950_O at the EcoNet thermostat. Rheem's fault page calls this 'Configuration Data Restore Failure' and states it means the firmware in the VSODC is corrupt and the control will need to be replaced. It adds an important caution: if you are reading only the d1 fault at the outdoor unit, check the EcoNet code when an EcoNet thermostat is installed, because d1 at the board can also correspond to an A951_O Memory Card Config Data Write Failure - two different faults sharing one board display, with different remedies.

Likely causes

  1. Corrupt firmware in the Variable Speed Outdoor Control (VSODC)
  2. Memory card configuration data write failure (EcoNet A951_O) presenting as d1 at the board
  3. Failed memory card or poor memory-card seating in the control
  4. Control board failure after a power surge or interruption during a write

How to fix it — step by step

  1. Record the code first: note d1 at the outdoor display, then read the exact fault at the EcoNet thermostat (A950_O versus A951_O) before cycling power - the thermostat code decides the remedy.
  2. Safety: turn power off at the outdoor disconnect and the breaker, verify dead with a meter, and observe capacitor caution before opening the control box.
  3. Locate the part: the VSODC is the main control board in the outdoor unit control box, with the memory card fitted to it.
  4. Test: reseat the memory card with power off and restore power; if the EcoNet fault is A951_O, a card rewrite or replacement may clear it, while a confirmed A950_O means, per Rheem, the VSODC firmware is corrupt and the control itself must be replaced - no field test repairs corrupt firmware.
  5. End at the fix: replace the memory card for a write failure or the control board for a restore failure, restore power to both units, and confirm the system is detected at the EcoNet thermostat with no d1 returning. → Shop the control board at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the d1 code

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manufacturer documentation

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.