Rheem Heat pump RP20 variable-speed heat pumps with Variable Speed Outdoor Control (VSODC) and EcoNet 48 Error Code

What the 48 code means

Read as 48 on the dual 7-segment LED of the Variable Speed Outdoor Control in the outdoor unit, and as EcoNet fault A961_O at the EcoNet thermostat. Rheem's fault page states this alarm means the compressor is not seeing voltage: the contactor does not appear to be pulling in, or line voltage is not getting through the contactor. In other words the control is calling for the compressor but no power is arriving at it. The page's checks separate a control-side failure (no 24 volts at the contactor coil, or a contactor that will not close) from a load-side failure (voltage lost between the contactor and the compressor, or an open compressor overload or winding).

Likely causes

  1. Contactor not pulling in - no 24 VAC at its coil or a failed coil
  2. Contactor contacts burned or pitted so voltage does not pass
  3. Broken or disconnected harness between contactor and compressor
  4. Compressor internal overload open or an open compressor winding

How to fix it — step by step

  1. Record the code first: note 48 (EcoNet A961_O) and whether the contactor audibly pulls in on a call, before cycling power.
  2. Safety: turn power off at the outdoor disconnect and the breaker, verify dead with a meter before resistance checks, and observe capacitor caution; voltage checks on a live call are pro work.
  3. Locate the part: the contactor is in the outdoor control box, with line voltage in at the bottom and the compressor harness leaving the load side.
  4. Test: per Rheem's page, confirm the contactor responds to a known 24 VAC at its magnetic coil; if it closes, measure voltage at the load side and check the compressor harness is intact. Then check windings: if C-R and C-S are open but R-S shows continuity, the internal overload is open - let the compressor cool and recheck, and check the capacitor.
  5. End at the fix: replace a contactor that will not pull in or pass voltage, repair the harness, or, if windings are genuinely open after cooling, the compressor has failed - EPA-tech replacement, call a pro. → Shop the contactor at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 48 code

Parts run $5–$35

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manufacturer documentation

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.