Rheem Heat pump RP20 variable-speed heat pumps with Variable Speed Outdoor Control (VSODC) and EcoNet 49 Error Code

What the 49 code means

Read as 49 on the dual 7-segment LED of the Variable Speed Outdoor Control in the outdoor unit, and as EcoNet fault A962_O at the EcoNet thermostat. Rheem's fault page states this alarm means the compressor is receiving voltage when the contactor should not be engaged - the opposite failure from code 48. A compressor that is powered during standby can run when it should be off, defeating the control's protection and short-cycling logic. The page directs the check to two places: a contactor whose contacts have welded shut, holding the circuit closed regardless of the coil, or a wiring error on the line-voltage or low-voltage side that keeps the contactor energized.

Likely causes

  1. Contactor contacts welded shut from repeated high-current starts
  2. Line-voltage wiring error feeding the compressor around the contactor
  3. Low-voltage wiring error holding the contactor coil energized
  4. Shorted wiring to the contactor coil

How to fix it — step by step

  1. Record the code first: note 49 (EcoNet A962_O) and whether the compressor is actually running or warm with no call, before cycling power.
  2. Safety: treat the compressor circuit as live even with the thermostat off - turn power off at the outdoor disconnect and the breaker, verify dead with a meter, and observe capacitor caution.
  3. Locate the part: the contactor is in the outdoor control box; inspect its contacts and both the line-voltage and low-voltage wiring to its coil.
  4. Test: with the coil de-energized, check continuity across the contactor's line contacts - continuity with the coil off proves welded contacts. No continuity means trace the coil circuit for the wiring error or short that is holding it in. → Shop the contactor at Amazon
  5. End at the fix: replace a welded contactor (and check the run capacitor and start currents that welded it), or correct the wiring fault, then restore power and confirm the compressor is unpowered in standby and starts only on a call.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the 49 code

Parts run $5–$35

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.