Armstrong Air Furnace G2D93CT / G2D95CT (System Sentry control) 4 flashes
What it should look like on your machine
then it repeats
4 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
High limit switch open. The furnace overheated during a heating cycle, so the control shut off the gas valve and combustion blower and runs the circulating blower on high speed until the limit closes.
Likely causes
- Dirty air filter or restricted airflow
- Closed registers or blocked returns
- Blower speed set too low or blower failing
- Faulty high limit switch
How to fix it — step by step
- Per the manual, when the limit senses abnormally high temperature the gas valve and combustion blower shut off and the circulating blower runs on high speed until the limit closes. Let it cool.
- Turn the power off and replace a dirty air filter. The manual calls for checking filters at least every 6 weeks.
- Open closed registers and clear the return grilles.
- Restore power and call for heat. Confirm the blower runs at full heat speed.
- If airflow is strong and trips repeat, turn the power off, find the high limit on the heat exchanger wall, and test it cold. Open when cold means it has failed.
- Replace a failed limit with the correct rated part. Trips that continue with good airflow need a pro to check firing rate and duct static.
- Verify the fix: restore power and run a full heat call from the thermostat and watch one complete heating cycle - ignition, steady burn and shutoff - the furnace should complete the cycle with no code returning. If it comes back, the fault is still present: recheck the step above whose result was borderline, and treat the part that step points to as the one to replace
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the air filter.
Also tied to this fault: high limit switch - Shop at Amazon
Parts that commonly fix it
- air filter$5–$30Shop at Amazon
- high limit switch$5–$35Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number inside the blower/burner compartment door. It's the key to the right manual pages and the right parts.
Related Armstrong Air Furnace G2D93CT / G2D95CT (System Sentry control) problems
See all Armstrong Air G2D93CT / G2D95CT (System Sentry control) codes & guides →