Armstrong Air Furnace G2D93CT / G2D95CT (System Sentry control) 1 flash
What it should look like on your machine
then it repeats
1 flash - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Flame present with the gas valve off. The control senses flame when no gas should be flowing.
Likely causes
- Gas valve leaking through or closing slowly
- Flame sensor wire shorted to ground
- Faulty flame sensor giving a false signal
How to fix it — step by step
- Turn the power off and close the gas shutoff to the furnace. Flame with the gas valve off is a safety fault.
- If you smell gas, leave the building and call the gas supplier from outside.
- With the gas off, find the flame sensor rod at the burners and inspect its wire for chafed insulation touching the cabinet. Repair any short.
- Confirm the burners are fully out with the valve off. Flame still present means the gas valve is leaking through.
- Do not run the furnace on this code. Gas valve work is pro work.
- Verify the fix: restore power and run a full heat call from the thermostat and watch one complete heating cycle - ignition, steady burn and shutoff - the furnace should complete the cycle with no code returning. If it comes back, the fault is still present: recheck the step above whose result was borderline, and treat the part that step points to as the one to replace
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the gas valve.
Parts that commonly fix it
- gas valve$100–$355Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number inside the blower/burner compartment door. It's the key to the right manual pages and the right parts.
Related Armstrong Air Furnace G2D93CT / G2D95CT (System Sentry control) problems
See all Armstrong Air G2D93CT / G2D95CT (System Sentry control) codes & guides →