Trane Heat pump ComfortLink communicating system with ACONT900AC43UA comfort control ERR 91 Error Code

What the ERR 91 code means

Shown as Err 91 on the Trane ComfortLink comfort control. The ACONT900 service manual gives several Error 91 communication-fault variants: SYS COMM ERR with loss of heat/cool demand - demand is generated every minute and a fault is reported after three missed messages - NO SYS CLK with the system clock not reporting and the Bit Master LED off, and BLW COMM ERR for loss of communication between the communicating blower motor and its control board. The outdoor and indoor fault LEDs and the exact interface text separate which link has actually failed.

Likely causes

  1. Data (D) line to the comfort control broken, disconnected, grounded, or reversed with B
  2. Indoor control board failure, including loss of the system clock
  3. No line voltage to the blower motor or a faulty low-voltage connection to it
  4. Voltage spikes or electrostatic discharge damaging a control board

How to fix it — step by step

  1. Record the code before cycling power: record Err 91 plus the exact interface text - SYS COMM ERR, NO SYS CLK or BLW COMM ERR - and the indoor fault LED count before cycling power. Power-cycling can clear, change or recount the fault, so note the display, operating mode and outdoor temperature first.
  2. Safety: turn the system off, open the outdoor disconnect and breaker, verify with a meter that the unit is dead before touching wiring, and stay clear of the run capacitor terminals - a capacitor can hold a shock charge with power off.
  3. Locate the part: inspect the D and B communicating wiring at the comfort control, indoor unit and outdoor unit; the indoor control board and its Bit Master LED are in the air handler or furnace cabinet
  4. Test: use the manual's voltage checks: about 12V DC between D and B at the indoor unit with 0V at the comfort control means a broken data line, and a Bit Master LED that is off, dim or flickering points to reversed or grounded data wiring at the outdoor unit
  5. End point: repair the data wiring if the tests point there; a clock that will not report with good wiring means replacing the indoor control board, which is pro work. Allow up to five minutes for the alert and LED to appear or clear after a change. Any work that opens the sealed refrigerant circuit, adjusts charge, or replaces a refrigerant pressure device is EPA-certified technician work only.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the ERR 91 code

  • Control boardShop at Amazon
  • Tools for this job, if you need them$15–$65

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Working on a specific model? The official Trane manual is on Trane's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related Trane Heat pump ComfortLink communicating system with ACONT900AC43UA comfort control error codes

See all Trane ComfortLink communicating system with ACONT900AC43UA comfort control codes & guides →