Trane Heat pump ComfortLink communicating system with ACONT900AC43UA comfort control ERR 79 Error Code

What the ERR 79 code means

Shown as Err 79 on the Trane ComfortLink comfort control, with the outdoor Fault LED flashing seven times. The ACONT900 service manual's Alert Code Response, Error 79: LPCO fault, describes an open low pressure switch: on 16 and 20 SEER systems a low-pressure cut-out open for the third time within the same call, a hard lockout reset by cycling power, with suction pressure thresholds given for cooling and heating, plus a heat/cool lockout variant at lower outdoor temperatures. It protects the compressor from running starved of refrigerant.

Likely causes

  1. System low on refrigerant charge
  2. Indoor airflow restriction in cooling, including a dirty air filter
  3. Outdoor airflow restriction in heating
  4. Wiring to the low pressure switch open or shorted, or power interrupted to the outdoor unit

How to fix it — step by step

  1. Record the code before cycling power: record Err 79 and whether the call was heating or cooling before cycling power to reset the hard lockout. Power-cycling can clear, change or recount the fault, so note the display, operating mode and outdoor temperature first.
  2. Safety: turn the system off, open the outdoor disconnect and breaker, verify with a meter that the unit is dead before touching wiring, and stay clear of the run capacitor terminals - a capacitor can hold a shock charge with power off.
  3. Locate the part: check the indoor air filter and both coils for restriction or ice; the low pressure switch is in the outdoor unit on the suction side
  4. Test: a technician with gauges verifies suction pressure against the manual's thresholds for the mode; pressure that is normal while the switch reads open condemns the switch or its wiring, and the manual warns a power interruption to the outdoor unit can also produce Err 79
  5. End point: fix airflow causes yourself. Low charge means leak search and repair by an EPA-certified technician; do not repeatedly power-cycle the lockout to force run time. Any work that opens the sealed refrigerant circuit, adjusts charge, or replaces a refrigerant pressure device is EPA-certified technician work only.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the ERR 79 code

Parts run $5–$30

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Working on a specific model? The official Trane manual is on Trane's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related Trane Heat pump ComfortLink communicating system with ACONT900AC43UA comfort control error codes

See all Trane ComfortLink communicating system with ACONT900AC43UA comfort control codes & guides →