Trane Heat pump ComfortLink communicating system with ACONT900AC43UA comfort control ERR 67 Error Code

What the ERR 67 code means

Shown as Err 67 on the Trane ComfortLink comfort control, with the outdoor Fault LED flashing five times for an ambient temperature sensor fault or six times for a coil temperature sensor fault. The ACONT900 service manual's Alert Code Response, Error 67: Temperature sensor fault, says the sensor is open or shorted - zero or infinite resistance - out of range against the literature chart, or the control board is outputting no voltage to it, expecting about 5V DC at the board with the sensor disconnected. Both sensors feed defrost and capacity decisions.

Likely causes

  1. Ambient or coil temperature sensor open or shorted
  2. Sensor resistance drifted out of range
  3. Damaged sensor harness or connector at the outdoor control board
  4. No sensor output voltage from the outdoor control board

How to fix it — step by step

  1. Record the code before cycling power: record Err 67 and then count the outdoor Fault LED flashes - five for ambient, six for coil - before cycling power. Power-cycling can clear, change or recount the fault, so note the display, operating mode and outdoor temperature first.
  2. Safety: turn the system off, open the outdoor disconnect and breaker, verify with a meter that the unit is dead before touching wiring, and stay clear of the run capacitor terminals - a capacitor can hold a shock charge with power off.
  3. Locate the part: both sensors are at the outdoor unit: the ambient sensor outside the coil, the coil sensor clipped to the coil, both wired to the outdoor control board in the control box
  4. Test: power off and measure the suspect sensor's resistance against the chart in the unit literature at the measured temperature; then, per the manual, check for about 5V DC from the control board with the sensor disconnected - no output voltage condemns the board, not the sensor → Shop the control board at Amazon
  5. End point: replace a sensor that tests open, shorted or off-chart; replace the control board only when a good sensor has no supply voltage or the fault persists with a known-good sensor. Any work that opens the sealed refrigerant circuit, adjusts charge, or replaces a refrigerant pressure device is EPA-certified technician work only.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the ERR 67 code

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Working on a specific model? The official Trane manual is on Trane's support site — you'll need your model number.

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.