Lennox Furnace SureLight two-LED control (DS1/DS2) — G40/G50/G51/G60/G61 series DS1 off, DS2 slow flash

What this problem usually means

On Lennox furnaces with the two-LED SureLight control (DS1 red, DS2 green; G40, G50, G51, G60, G61 series), DS1 off with DS2 slow flash means the low pressure switch is open — it failed to close, or was closed before the inducer started.

Likely causes

  1. Blocked intake or exhaust vent
  2. Clogged or frozen condensate drain
  3. Failed inducer motor → Shop the inducer motor at RepairClinic
  4. Failed pressure switch

How to fix it — step by step

  1. Clear snow, ice or debris from the outdoor intake and exhaust
  2. Check the condensate drain for clogs or freezing
  3. Reset power once (off 30 seconds, then on)
  4. Call a technician if it returns, to test the inducer and pressure switch → Shop the pressure switch at RepairClinic

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.