Ruud Heat pump RHPBZR Series heat pumps - Enhanced Feature Demand Defrost Control LED 1 OFF / LED 2 OFF Error Code
What the LED 1 OFF / LED 2 OFF code means
Read on the two diagnostic LEDs of the Enhanced Feature Demand Defrost Control inside the outdoor unit, as charted in the Ruud RHPBZR installation instructions. Both LEDs dark is the chart's 'No Power' status: the defrost control board has no power to operate with, so it cannot run the compressor or outdoor fan, read its coil and ambient sensors, apply high- and low-pressure protection, or time a defrost. This is a control power-supply indication, not a refrigerant fault, and no other pattern on this board can be read or trusted until board power is restored and proven.
Likely causes
- No 24 VAC control power reaching the defrost board from the indoor unit or transformer
- Tripped breaker or open outdoor disconnect cutting power to the system
- Blown low-voltage fuse or a loose or broken control wire at the board
- Failed defrost control board
How to fix it — step by step
- Record the code first: note both LEDs dark and whether the thermostat is calling, before cycling any power.
- Safety: turn power off at the outdoor disconnect and the breaker, verify the unit is dead with a meter, and treat the run capacitor as charged until discharged.
- Locate the part: remove the outdoor unit control-box cover to reach the defrost control board and its control-power terminals.
- Test: restore power briefly and measure control voltage at the board; about 24 VAC present with both LEDs still dark condemns the board, while 0 VAC means the loss is upstream in the fuse, transformer or control wiring - trace it until power is restored.
- End at the fix: repair the upstream power fault or replace the defrost control board, then confirm the LEDs show the normal pattern on a call. → Shop the defrost control board at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the Defrost control board.
Parts that commonly fix the LED 1 OFF / LED 2 OFF code
- Defrost control boardShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related Ruud Heat pump RHPBZR Series heat pumps - Enhanced Feature Demand Defrost Control error codes
- LED 1 OFF / LED 2 ON
- LED 1 ON / LED 2 FLASH
- LED 1 ON / LED 2 ON
- LED 1 FLASH / LED 2 OFF
- LED 1 FLASH / LED 2 ON
- LED 1 OFF / LED 2 FLASH
See all Ruud RHPBZR Series heat pumps - Enhanced Feature Demand Defrost Control codes & guides →