Payne Furnace 23.3 Error Code

What the 23.3 code means

Over pressure at start-up on the Payne PG80MSU (3-digit display model with pressure transducer). The LED flashes major code 23 while the display reads 23.3: the pressure transducer output is above 0.65 Vdc at the start of the heating sequence, so the control delays ignition until the signal returns to range.

Likely causes

  1. Defective pressure transducer or transducer wiring
  2. Obstruction in the pressure tubing
  3. Improper vent sizing
  4. Excessive wind at the vent termination

How to fix it — step by step

  1. Check outdoor intake and exhaust terminations for snow, ice or debris
  2. Note the code for the technician
  3. Do not open the furnace cabinet to test the transducer yourself
  4. Call a technician - the transducer and its tubing are inside the cabinet and need professional testing

Parts that commonly fix the 23.3 code

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.