Trane Heat pump 4TWR5042H1000A split system heat pump 4 flashes
What it should look like on your machine
then it repeats
4 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Read on the Fault LED of the demand defrost control board inside the outdoor control box. Table 3, LED Fault Codes, in the Trane Service Facts calls four flashes a hard lock out that can only be cleared with a low-voltage power cycle, and its notes say it occurs after the ninth trip of the low-pressure cut-out. The system will not restart on its own. It matters because nine low-pressure trips mean the underlying cause - usually lost charge or a serious airflow problem - was never fixed; clearing the lockout without diagnosis invites compressor damage.
Likely causes
- Repeated low-pressure cut-out trips from low refrigerant charge
- Severe airflow restriction at the indoor or outdoor coil
- Outdoor fan motor not running during heating
- Low pressure switch or wiring fault producing false trips
How to fix it — step by step
- Record the code before cycling power: count four flashes and count on the unit staying off - this is a hard lockout. Power-cycling can clear, change or recount the fault, so note the display, operating mode and outdoor temperature first.
- Safety: turn the system off, open the outdoor disconnect and breaker, verify with a meter that the unit is dead before touching wiring, and stay clear of the run capacitor terminals - a capacitor can hold a shock charge with power off.
- Locate the part: the defrost board is in the outdoor control box; check the indoor filter and outdoor coil and fan before any reset attempt
- Test: note the trip history pattern in the Service Facts: earlier trips gave timed soft lockouts, the ninth gives this hard lockout. A technician must measure suction pressure with gauges to separate a real low-charge condition from a switch that opens at normal pressure
- End point: have a technician find and repair the cause of the repeated trips, then clear the lockout with a low-voltage power cycle as the manual specifies. Repeated DIY resets without repair risk the compressor. Any work that opens the sealed refrigerant circuit, adjusts charge, or replaces a refrigerant pressure device is EPA-certified technician work only.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Air filter.
Also tied to this fault: Outdoor fan motor - Shop at Amazon; Defrost control board - Shop at Amazon
Parts that commonly fix it
- Air filter$5–$30Shop at Amazon
- Outdoor fan motorShop at Amazon
- Defrost control boardShop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Working on a specific model? The official Trane manual is on Trane's support site — you'll need your model number.
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.