What the E218 code means

E218 is a heating return thermistor open or short circuit, shown as an alarm. The boiler has lost its heating return temperature reading, which it uses to control firing and efficiency. The cause is the return thermistor or its wiring.

Likely causes

  1. Heating return thermistor open circuit
  2. Heating return thermistor short circuit
  3. Thermistor wiring fault

How to fix it — step by step

  1. Record the code before resetting: write down E218 exactly as shown on the NCB-H front panel display, and note whether heating, hot water, or both were running.
  2. Safety: if you smell gas, do not touch electrical switches, leave and call the gas supplier from outside. Otherwise turn the boiler off and close its manual gas shut-off valve before any cover comes off, and keep gas, burner and vent work to a qualified installer.
  3. Locate the parts: the heating return thermistor is fitted on the heating return waterway at the bottom of the boiler and wired to the main PCB; E218 is read on the front panel display.
  4. Test: a technician measures the return thermistor against the expected resistance for the return water temperature and checks its harness. Open or shorted at the sensor condemns the sensor; a correct sensor reading moves the fault to the wiring.
  5. End at the fix: replace the heating return thermistor if it tests faulty, or repair the harness if it tests good. The alarm clears when a valid return reading returns.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the E218 code

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Navien Boiler NCB-H series error codes

See all Navien NCB-H series codes & guides →