Cummins Generator QuietConnect RS13A / RS17A / RS20A / RS20AC (GSBB/GSBC) Code 79 - Failure to Transfer to Generator Set

What this problem usually means

The transfer switch failed to transfer the load to the generator set. The generator may run correctly while the house stays dark, because the fault is in the transfer path, not the engine.

Likely causes

  1. Generator set main AC circuit breaker off
  2. Wire connections
  3. Faulty positional switch
  4. Faulty transfer switch component

How to fix it — step by step

  1. Warning: never open a transfer switch or try to force a transfer by hand. Transfer equipment connects utility and generator power, and a wrong move can backfeed the utility lines and kill a line worker.
  2. Verify that the main AC circuit breaker on the generator set is On. Access is at the generator set breaker, not inside the transfer switch. A breaker found off, reset to On, with transfer then working, is the completed fix.
  3. If the breaker is On and transfer still fails, the pinpoint is the positional switch, wiring or a transfer switch component. Have the unit serviced by an authorized Cummins dealer and report Code 79.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

This fault usually does not need a replacement part - the fix is in the steps above. If your generator does need a part, start with the link above.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.