Cummins Generator QuietConnect RS13A / RS17A / RS20A / RS20AC (GSBB/GSBC) Code 15 - Underfrequency
What this problem usually means
Output frequency fell too low and the set shut down. The engine is running slow for the load placed on it, or its governing and fuel side cannot hold speed.
Likely causes
- Too many connected loads, especially high starting-current loads such as air conditioners
- Engine governor function
- Fuel supply or air fuel mixture
- Ignition, choke, demand regulator or carburetor fault
- Exhaust system fault
- Generator windings or wire connections
How to fix it — step by step
- Reduce the number of connected loads, especially loads that require higher starting current such as air conditioners. That load reduction is the owner test for this code.
- Clear the fault and run the set on the reduced load. Frequency holding with no Code 15 confirms overload was the cause, and the fix is keeping the load within the set rating.
- If the code returns on a light load, the pinpoint is governor, fuel or ignition. Have the unit serviced by an authorized Cummins dealer and report Code 15 with the load you tested at.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the fault is internal - there is no documented owner fix beyond the steps above. If you're not comfortable taking it apart yourself, a repair shop is the next step.
Parts that commonly fix it
This fault usually does not need a replacement part - the fix is in the steps above. If your generator does need a part, start with the link above.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.
Related Cummins Generator QuietConnect RS13A / RS17A / RS20A / RS20AC (GSBB/GSBC) problems
- Code 2 - Low Oil Pressure
- Code 29 - High Battery Voltage
- Code 32 - Low Cranking Speed Sense
- Code 35 - Control Card Failure
- Code 36 - Stopped Without Fault Condition
- Code 4 - Overcrank
- Code 79 - Failure to Transfer to Generator Set
- Does Not Transfer
- Won't Start
- Won't Turn On
- Code 12 - Overvoltage
- Code 13 - Undervoltage
See all Cummins QuietConnect RS13A / RS17A / RS20A / RS20AC (GSBB/GSBC) codes & guides →